Box and Conduit Fill Calculations

August 15, 2016 | Author: Pauline Turner | Category: N/A
Share Embed Donate


Short Description

1 Box and Conduit Fill Calculations2 3 Volume required per conductor4 5 6 Conduit fill - Box sizing Table (a) : Number o...

Description

Box & conduit Fill Calculations

Box and Conduit Fill Calculations

Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

Volume required per conductor

Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

Conduit fill - Box sizing Table 314.16(a) : Number of conductors in box 600v, nominal or less

CONDUCTORS: 1.

Conductors originating outside box, terminating in box count as 1 conductor

2.

Conductors originating outside box, spliced in box counts as 1 conductor

3.

A conductor entering a box, spliced to a conductor leaving box counts as 2 conductors

4.

Conductors passing through box without splices or terminations count as 1 conductor

5.

A conductor of which no part leaves the box shall not be counted Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

Conduit fill - Box sizing

2005 NEC Change

Looped conductors now count as 2 conductors

Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

EQUIPMENT GROUNDING CONDUCTOR:

1.

One, two or more bare, insulated or covered system grounding conductors all count the same size, count as 1 conductor

2.

One, two or more bare, insulated or covered system grounding conductors of various sizes, count as one conductor based upon largest equipment grounding conductor

3.

A separate ‘ISOLATED’ equipment grounding conductor counts as 1 conductor in addition to system grounding conductor. Count as size of ‘ISOLATED’ grounding conductor or largest if various sizes.

Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

CLAMPS: 1. Clamps installed inside box by factory count as 1 conductor 2. Clamps installed in box in the field count as 1 conductor (Conductor size based on largest conductor in box)

SUPPORT FITTINGS: 1. Fixture studs count as 1 conductor 2. Fixture hickeys count as 1 conductor (Conductor size based on largest conductor in box)

Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

DEVICE(S) IN BOX: 1.

Yoke or strap with switch, counts as 2 conductors

2.

Yoke or strap with duplex receptacle counts as 2 conductors

3.

Yoke or strap with triplex receptacle counts as 2 conductors

4.

Yoke or strap with switch & light on same yoke or strap counts as 2 conductors

5.

Yoke with any combination of three devices on same yoke or strap counts as 2 conductors

(Conductor size based on LARGEST conductor connected to device or equipment)

Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

Yoke or Strap

Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

Conductor Counts for other than wire Cable Clamps

NM 12-2 W/GRD

Hickey Fixture Stud

Fixture Stud

=

1 Conductor

Hickey

=

1 Conductor

Cable Clamps (2)

=

1 Conductor

Total Conductor Count =

3 Conductors

Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

Counting Devices 1 Yoke 1 Device 1 Conductor

1 Yoke 3 Devices 1 Conductor

1 Yoke 1 Device 1 Conductor 1 Yoke 2 Devices 1 Conductor

Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

Terminate in Box

Through Box

Through Box 2 Terminate in Box 4 Total Count = 6

All Conductors Terminate in Box Count 6 total conductors Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

Factory installed clamps 8-12’s & 1 clamp = 9

Factory or Field Installed Clamps

#12 AWG

#12 AWG

Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations EGC = Equipment Grounding Conductor IEGC = Insolated Equipment Grounding Conductor BJ = Bonding Jumper

EGC = 1 IEGC = 2 BJ = 0 Total = 2 BJ

EGC

IEGC

To Receptacle Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

Octagonal / 4/0 Box

2 - #8 AWG

2 - #12 AWG

2 - #12 AWG

2 - #8 @3.00 Cu Fix Stud @3.00 Cu in 4 - #12 @2.25 Cu in Total

= = = =

6 Cu in 3 Cu in 9 Cu in 18 Cu in

Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations #8 AWG #14 Bare EGC #12 AWG

#18 AWG fixture wire #10 AWG #18 = 1.5 cu in x 2 #14 = 2.0 cu in x 1 #12 = 2.25 cu in x 4 #10 = 2.50 cu in x 2 #8 = 3.00 cu in x 2 Fix Stud = #8 = 3.00 cu in

= = = = = =

3.00 cu in 2.00 cu in 9.00 cu in 5.00 cu in 6.00 cu in 3.00 cu in

Total Box volume required = 28,00 cu in Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

Bad Planning

Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

314.16(b)(1) Exception Canopy Cover 4 - Smaller than #14 Fixture wires

EGC

Dome Canopy Terminations in Canopy Cover To Fixture To Fan

Do not count for Box Fill Calculations Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

Counting with a device 2 - #8 AWG

2 - #12 AWG Largest conductor allowed = #10 NEC 110.14(A) 2 - #12 AWG

2 - #8 @3.00 cu in = 6 cu in 4 - #12 @2.25 cu in = 9 cu in Yoke @2.25 cu in = 4.5 cu in Total Volume Required = 19.5 cu in Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

Conduit Fill Calculations

Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

Major Fraction Change

Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

What size EMT is needed for 3 - 2/0 AWG THW Cu conductors and 4 - 4/0 AWG THHN Cu conductors ?

Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

What size EMT is needed for 3 - 2/0 AWG THW Cu conductors and 4 - 4/0 AWG THHN Cu conductors ? Table 5 – Cross-Sectional Area of Individual Conductors 2/0 AWG THW Cu

=

.2624 X 3

4/0 AWG THHN Cu

=

.3237 X 4 =

1.2984

=

2.0820

Total Square Inches for Conductors

=

.7872

Table 4 – 40% fill column for “Over 2 wires”. 2.0820 Sq.In.

Requires a 2 ½ inch EMT Conduit

40% fill for 2 ½ inch EMT =

2.343 Sq. In.

Answer = 2 ½ Inch EMT Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

What size IMC is required for 6 - 12 AWG RHH Cu conductors without outer covering and 4 -14 AWG RHH Cu Conductors with outer covering ?

Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

What size IMC is required for 6 - 12 AWG RHH Cu conductors without outer covering and 4 -14 AWG RHH Cu Conductors with outer covering ? Table 5 – Cross-Sectional Area of Individual Conductors 14 AWG RHH Cu With Outer Covering

=

.0293 X 4

=

.1172

12 AWG RHH Cu Without Outer Covering

=

.0260 X 6 =

.1560

=

.2732

Total Square Inches for Conductors Table 4 – 40% fill column for “Over 2 wires”. .2732 Sq.In.

Requires a 1 inch IMC Conduit

40% fill for 1 inch IMC

=

.384 Sq. In.

Answer = 1 Inch IMC Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

Box & Conduit Fill Exam 10 Questions 30 Minutes

Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

Box fill Answers 1. (b) 10.75 cu in

314.16(b) 3 - #12’s @ 2.25 cu in = 6.75 cu in 2 - #14’s @ 2.00 cu in = 4.00 cu in 10.75 cu in

2. (b) 2 conductors

314.16 (b)

3. (b) 4

Table 314.16(a)

4. (d) 17.5 cu in

Table 314.16(b) #10 = 2.5 cu in 7 - #10’s x 2.5 cu in = 17.5 cu in

5. (a) 0.0181 in2

Table 5 (note * notations by insulations) * ONLY APPLIES TO RHH,RHW,RHW-2

Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

Box fill Answers 6. (d)

39.75 cu in

Table 314.16(b) #8 = 3.00 cu in #12 = 2.25 cu in Clamps -

#8 = 3.00 cu in

7 - #8 @ 3.00 cu in = 21.00 cu in 1 - #8 @ 3.00 cu in = 3.00 cu in 7 - #12 @ 2.25 cu in = 15.75 cu in 39.75 cu in

Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

3 - #8 ungrounded conductors count as

3 {314.16(b)(1)}

3 - #8 grounded conductors count as

3 {314.16(b)(1)}

3 - #8 grounding conductors count as

1 {314.16(b)(5)}

4 - clamps count as

1 {314.16(b)(2)}

3 - #12 ungrounded conductors count as

3 {314.16(b)(1)}

3 - #12 grounded conductors count as

3 {314.16(b)(1)}

3 - #12 grounding conductors count as

1 {314.16(b)(5)}

#8 conductors

7 - #8 @ 3.00 cu in = 21.00 cu in

Clamps

1 - #8 @ 3.00 cu in = 3.00 cu in

#12 conductors

7 - #12 @ 2.25 cu in = 15.75 cu in 39.75 cu in

Copyright 1999-2007 Dan Dudley

Box & conduit Fill Calculations

7.

(b)

2.2831 in²

T.5

8.

(b)

1 1/4” IMC

T.4

9.

(a)

.384in²

T.4

.2637in²

T.5

10. (C)

Copyright 1999-2007 Dan Dudley

View more...

Comments

Copyright � 2017 SILO Inc.